Non-Pressurized Ultra-Fine Dry Powder Fire Extinguishing Device (Wall-Mounted Type)
Category:
This device adopts a new type of propellant (solid-to-gas conversion), offering superior performance compared to gas-based propellants used in similar products.
Overview
This device adopts a new type of propellant (solid-to-gas conversion), offering superior performance compared to gas-based propellants used in similar products. It features low noise, minimal recoil, and extended discharge duration. When multiple devices are activated in linkage, they do not cause secondary damage to the protected objects or the building structure. The use of a small nozzle and powder-dispersing disc allows the ultra-fine dry powder extinguishing agent to fully demonstrate its high-efficiency fire suppression capabilities, making it an ideal next-generation automatic fire suppression product.
Working Principle
When a start signal is received (either automatically or manually), the initiator ignites the gas-generating agent, which is then activated to rapidly produce gas. This gas quickly expands inside the device’s casing, increasing internal pressure. Once the pressure reaches a predetermined level, the gas fully mixes with the ultra-fine dry powder and breaks through the aluminum membrane at the nozzle. The extinguishing agent is then rapidly discharged into the protected area, quickly spreading outward to form a total-flooding mist-like suppression state. The flame is extinguished through both the physical and chemical actions of the ultra-fine dry powder.
Basic Parameters
|
Model Specification |
FFB-ACT3-WK |
FFB-ACT5-WK |
FFB-ACT8-WK |
|
Extinguishing Agent Weight (Kg) |
3 |
5 |
8 |
|
Dimensions (Diameter × Total Height) |
φ510*335*300 |
φ520*385*300 |
φ580*395*300 |
|
Total Weight of the Device (kg) |
12 |
15 |
19 |
|
Protected Volume (㎥) |
22 |
36 |
57 |
|
Local Extinguishing Capability (A/B) |
1A/34B |
1A/55B |
2A/89B |
|
Activation Parameters |
Electric Activation: DC 24V ≤ 1.0A Thermal Sensor Wire Activation: 170 ± 10°C |
||
|
Applicable Temperature (℃) |
-40~50 |
||
|
Discharge Time (S) |
≤5s |
≤5s |
≤10s |
|
Fire Type Classification |
Class A, B, C, and electrical fires |
||
|
Note: Model designation of the non-pressurized ultra-fine dry powder fire extinguishing device is as follows, e.g., FFB-ACT5-WK. F-Dry powder fire extinguishing device;F-Non-pressurized type;B-Wall-mounted type;A-ABC dry powder;T- For general-purpose applications;5-5 kg of dry powder;WK-Weiken brand logo trademark. |
|||
Related Products
Product Inquiry
We highly value your feedback and inquiries. If you have any questions about our products or services, please fill out the form below, and we’ll get in touch with you as soon as possible.