Pressurized Ultra-Fine Dry Powder Fire Extinguishing Device


This device employs two scientifically optimized activation methods to enable early fire detection and suppression, effectively minimizing fire-related losses.

Hotline:

Overview

This device employs two scientifically optimized activation methods to enable early fire detection and suppression, effectively minimizing fire-related losses.

Working Principles:

1、Fixed Temperature Activation:When a fire occurs and the ambient temperature rises to the preset value of the fire extinguishing device, the temperature-sensitive auto-activation mechanism is triggered, releasing the ultrafine dry powder extinguishing agent to suppress the fire.

2、Electric Control Linkage Activation:The controller of the hanging fire extinguishing device can be connected to any fire alarm control panel. When the fire detector senses a fire signal and the controller confirms the presence of a fire, the extinguishing device automatically discharges the agent to suppress it.

3、Manual Activation:In the event of a fire, on-duty personnel can press the manual activation button located outside the protected area to trigger the extinguishing device.

This fire extinguishing device consists of an agent storage tank, ultrafine dry powder extinguishing agent, omnidirectional spray nozzle, thermal or electrical activation mechanism, mounting brackets, and other components.

Basic Parameters

Model Specification

Extinguishing Agent Weight (Kg)

Dimensions (Diameter × Total Height)

Protected Volume (㎥)

Local Extinguishing Capability (A/B)

Activation Parameters

Applicable Temperature (℃)

Discharge Time (S)

Service Life

Fire Type Classification

FZX-ACT2/1.2-WK

2

φ210*180

15.4

1A/34B

 

 

 

 

 

 

 

 

 

 

 

DC24V (≤1.5A); Thermal activation: 68℃

 

 

 

 

 

 

 

 

 

 

 

-10~50

 

 

 

 

 

<5

   

 

 

 

 

10 years

 

 

 

 

 

 

 

 

Class A, B, C, and electrical fires

FZX-ACT3/1.2-WK

 

3

φ266*191

20

1A/34B

 

FZX-ACT4/1.2-WK

 

4

φ266*223

30.8

1A/34B

 

FZX-ACT5/1.2-WK

 

5

φ300*238

33

1A/34B

 

FZX-ACT6/1.2-WK

 

6

φ300*258

46.2

1A/34B

 

 

 

 

 

 

 

<10

FZX-ACT7/1.2-WK

 

7

φ300*258

46.2

2A/89B

FZX-ACT8/1.2-WK

 

8

φ300*320

46

2A/55B

FZX-ACT10/1.2-WK

 

10

φ300*320

53

2A/89B

FZX-ACT12/1.2-WK

 

12

φ370*290

67

2A/89B

 

<15

FZX-ACT3/1.5-WK

 

3

φ266*191

25

1A/34B

 

 

 

 

DC24V (≤1.5A); Thermal activation: 68℃; Heat triggered: 170℃

 

 

 

 

 

-10~50

 

 

 

<5

 

 

 

 

 

10 years

 

 

 

 

 

Class A, B, C, and electrical fires

FZX-ACT4/1.5-WK

4

φ266*223

33.3

2A/55B

FZX-ACT5.5/1.5-WK

5.5

φ300*238

45.8

2A/55B

FZX-ACT8/1.5-WK

8

φ300*320

66.7

3A/89B

 

 

<15

FZX-ACT10/1.5-WK

10

φ300*320

83.3

3A/89B