Internally Pressurized Perfluorohexanone Fire Extinguishing Device
Category:
The perfluorohexanone fire extinguishing device is a compact, pressure-free storage gas-based fixed fire suppression system that utilizes perfluorohexanone as the extinguishing agent.
Overview
1. Introduction to the Perfluorohexanone Fire Extinguishing Device
The perfluorohexanone fire extinguishing device is a compact, pressure-free storage gas-based fixed fire suppression system that utilizes perfluorohexanone as the extinguishing agent. It is designed with reference to aerospace and military equipment design experience and incorporates independently developed innovative technologies. The device operates by releasing pressure through an integrated pressurization drive module, which rapidly discharges the perfluorohexanone extinguishing agent from the main unit. It is particularly suitable for fire protection in small, enclosed spaces.
This system can quickly extinguish Class A, B, C, and E fires within the protected area. It is compatible with various types of fire detectors, allowing for uninterrupted and continuous monitoring in both occupied and unoccupied environments. The system accurately detects early fire signals and executes effective fire suppression.
2. Application Areas
Perfluorohexanone is a liquid at room temperature and produces other gases upon thermal decomposition at high temperatures. Once atomized, the perfluorohexanone extinguishing agent functions as part of an automatic gaseous fire suppression system. It is suitable for use in environments such as high- and low-voltage distribution boxes, electrical cabinets, lithium battery storage cabinets, lithium battery thermostatic chambers, lithium battery energy storage systems, vehicle engine compartments, precision equipment, printing presses, offset printing machines, heat treatment quenching equipment, cold and hot rolling machines, paper manufacturing and burning equipment, high-temperature air ducts, high-temperature flue systems, deep-frying machinery, and CNC machines.
Basic Parameters
|
Product model and specifications |
YF1/1.6-N-Y-WK |
|
Fire extinguishing agent storage bottle volume (L) |
1 |
|
Device diameter (mm) |
85 |
|
Device height (mm) |
330 |
|
Storage pressure of fire extinguishing agent |
1.6 MPa(20℃) |
|
Maximum work pressure |
2.0 MPa(50℃) |
|
Density of fire extinguishing agent filling |
≤ 1420Kg/m³ |
|
Startup method |
Fixed temperature sensing glass ball: Starting temperature: 68 ℃ Electric starting: DC24V(0.5A-1.5A) |
|
Fire extinguishing methods |
Completely submerged |
|
Fire extinguishing agent spraying time |
≤ 10S |
|
Drive gas |
Nitrogen gas |
|
Environmental temperature for use |
0℃~50℃ |