Non-Pressurized Perfluorohexanone Fire Suppression Device
Category:
The Perfluorohexanone Fire Suppression Device is a small, non-pressurized, fixed gas fire suppression system designed using aerospace and military equipment principles with independent innovative technology.
1. Introduction to Perfluorohexanone Fire Suppression Device
The Perfluorohexanone Fire Suppression Device is a small, non-pressurized, fixed gas fire suppression system designed using aerospace and military equipment principles with independent innovative technology. It utilizes perfluorohexanone as the extinguishing agent and employs an integrated pressurization drive module to release pressure, rapidly propelling the extinguishing agent from the main unit. This makes it particularly suitable for fire protection in small spaces.
The device can quickly extinguish Class A, B, C, and E fires within the protected area. Additionally, it is compatible with multiple types of fire detectors, enabling continuous monitoring in both occupied and unoccupied environments. This allows for early fire detection and effective suppression.
2. Application Areas
At room temperature, perfluorohexanone is in liquid form, but upon exposure to high temperatures, it undergoes thermal decomposition, generating other gases. When atomized, the perfluorohexanone extinguishing agent forms a gas-based automatic fire suppression system, making it suitable for applications such as:
● High- and low-voltage distribution boxes
● Electrical cabinets
● Lithium battery energy storage cabinets
● Lithium battery thermostatic chambers
● Lithium battery energy storage systems
● Automobile engine compartments
● Precision equipment
● Printing machines & offset printing machines
● Heat treatment & quenching equipment
● Cold rolling & hot rolling machines
● Paper manufacturing & sintering equipment
● High-temperature air ducts & flue systems
● Frying machinery
● CNC machines
Basic Parameters
|
Model specification |
Dimensions (mm) |
Extinguishing Agent Weight |
Protected Volume |
|
YF0.1Q-WK |
145*96*16mm |
100g±2% |
≤0.1m³ |
|
YF0.13Q-WK |
145*96*16mm |
130g±2% |
≤0.14m³ |
|
YF0.20-Q-Y-WK |
285*62*72mm |
200g±2% |
≤0.22m³ |
|
YF0.35-Q-Y-WK |
060*370mm |
350g±2% |
≤0.4m³ |
|
YF0.5-Q-Y-WK |
345*72*62mm |
500g±2% |
≤0.56m³ |
|
YF0.8-Q-Y-WK |
500*60*60mm |
800±2% |
≤0.9m³ |
|
YF0.9-Q-Y-WK |
060*670mm |
900±2% |
≤1.0m³ |
|
YF1.0-Q-Y-WK |
530*75*75mm |
1.0kg |
≤1.1m³ |
|
YF1.5-Q-Y-WK |
Ø78*540mm |
1.5kg |
≤1.7m³ |
|
YF2.0-Q-Y-WK |
695*75*75mm |
2.0kg |
≤2.2m³ |
|
YF10-Q-Y-WK |
700*260*170mm |
10.0kg |
≤11.3m³ |
|
Discharge Time |
≤8s |
Extinguishing Time |
≤30s |
|
Extinguishing Density |
≥0.88kg/m³ |
Fire Suppression Device Activation Temperature |
≤170℃ |
|
Operating Temperature Range |
-40℃~+80℃ |
Activation Method |
Electric/Thermal Activation, Temperature-Sensitive Magnetic Power Generation |
|
Activation Current |
≥0.5A |
Temperature-Sensitive Magnetic Power Generation Activation Condition |
93℃±5% |
|
Service Life |
≥10 |
Fire Suppression Device with Activation Feedback Function |
Compliant; Normal Operation:Normally open After Activation:Normally closed |
|
Activation Voltage |
≤DC24V |