Fire Detection Tube Fire Extinguishing System (Direct Type)


The fire detection tube fire extinguishing system consists of an extinguishing agent bottle group, fire detection tube, signal feedback device, and more.

Hotline:

Overview

The fire detection tube fire extinguishing system consists of an extinguishing agent bottle group, fire detection tube, signal feedback device, and more. The fire detection tube fire extinguishing system produced by our company uses FM200/CO2 as the extinguishing agent. It is a simple, low-cost, and highly reliable independent automatic fire extinguishing system. This system does not require any power supply, specialized smoke or temperature detectors, or complex equipment and pipelines. It relies on its own stored pressure and utilizes a pre-pressurized fire detection tube and a set of fire detection bottles to quickly, accurately, and effectively extinguish fire sources. This system integrates both alarm and extinguishing functions to suppress fire hazards in their initial stage. It significantly reduces engineering costs, lowers the cost of each firefighting operation, and ensures no harm to personnel. By using the fire detection device, it allows for the protection of valuable equipment in small, enclosed spaces, as opposed to just large rooms in closed spaces. The system uses a flexible and bendable fire detection tube as the fire detection component, which also acts as the conduit for the extinguishing agent’s delivery and release. This tube can be easily laid out close to any potential ignition point, offering extremely high extinguishing efficiency.

Fire Extinguishing Principle

The fire detection tube gas fire extinguishing system is a new type of non-electrical self-starting fire extinguishing system, also known as the temperature-sensitive self-starting fire extinguishing device. It directly detects fire, transports, and sprays the extinguishing agent through a fixed fire detection tube connected to a fixed extinguishing agent supply source. This system sprays a certain concentration of extinguishing agent into the protected area, filling the area evenly to extinguish the fire.

Features of the Fire Extinguishing System

● Alarm and extinguishing functions combined: It has a quick detection and response time, provides point-to-point fire extinguishing, and can quickly suppress the fire in its early stages, effectively reducing economic losses caused by fires.

● No power required: The system is not affected by vibration or collision, does not weaken or cause false alarms due to oil, dust, or smoke interference, and is immune to electromagnetic, humidity, heat, and dust interferences, making it safer and more reliable for protecting electrical equipment.

● Flexible fire detection tube: The fire detection tube is flexible and unaffected by positioning, allowing it to be inserted into narrow or complex combustible spaces or equipment. This feature overcomes the limitations of existing fire protection products that cannot handle such fire sources.

● High extinguishing efficiency and low cost: The system can be installed closer to the protected items, ensuring high extinguishing efficiency at a lower cost.

● Less extinguishing agent usage: The system uses less extinguishing agent than traditional methods, making it more environmentally friendly and safer for personnel.

● Ideal for unmanned and key protection areas: It is particularly suitable for environments requiring protection but without the need for regular human presence.

● Simple design and installation: The system is easy to install, does not occupy much space, and does not require a separate cylinder room.

Basic Parameters

Model Specifications

TH-Z-Q-3/2.5/170-WK

TH-Z-Q-6/170-WK

TH-Z-E-6/170-WK

Product Type

Direct

直接

直接

Extinguishing Agent Cylinder Capacity (L)

5

8

15

Detection Tube Specification

φ8*1

φ8*1

φ8*1

Detection Tube Static Activation Temperature (℃)

170±10

170±10

 

170±10

Detection Tube Charging Pressure (MPa)

1.5

1.5

1.5

Storage Working Pressure (at 20℃)

2.5MPa

2.5MPa

5.7MPa

Extinguishing Agent Type

HFC-227ea (Heptafluoropropane)

HFC-227ea (Heptafluoropropane)

Carbon Dioxide (CO₂)

Extinguishing Agent Filling Weight (kg)

3

6

6

Maximum Length of Detection Tube (m)

25

25

25

Operating Environment Temperature (℃)

0-50

0-50

0-50

Note:The model of the direct-type automatic fire detection and extinguishing device using heptafluoropropane detection tube is represented as follows:

Example: TH-Z-Q-3/2.5/170-WK

TH: Detection Tube Fire Extinguishing Device

Z: Direct Type

Q: Heptafluoropropane Extinguishing Agent

3: Filling Weight of the Extinguishing Agent (kg)

2.5: Storage Pressure is 2.5 MPa

170: Activation Temperature is 170℃

WK: Weiken logo mark

 