Water-Based Fire Extinguisher
Category:
The water-based fire extinguisher is an environmentally friendly, new-generation, and highly efficient fire suppression product. It is filled with a water-based extinguishing agent that provides both cooling and chemical inhibition effects. It is capable of extinguishing:
Overview
The water-based fire extinguisher is an environmentally friendly, new-generation, and highly efficient fire suppression product. It is filled with a water-based extinguishing agent that provides both cooling and chemical inhibition effects. It is capable of extinguishing:
Class A fires (ordinary solid materials)
Class B fires (flammable liquids)
Class E fires (electrical equipment)
Class F fires (cooking oil and grease)
Important Note:
When extinguishing Class E (electrical) fires, maintain a distance of at least 1 meter between the nozzle and the flames. Do not use this extinguisher on electrical fires involving voltages higher than 1kV!
Basic Parameters
|
Model |
MS/ABEF2 |
MS/ABEF3 MS/ABEF3 I (Low Temp) |
MS/ABEF6 MS/ABEF6 I(Low Temp)
|
MS/ABEF9 |
MSTW/ABE25 MSTE/ABE25 I(Low Temp) |
MSTW/ABE45 |
|
Extinguisher Dimensions (Diameter × Height)mm |
φ110*403 |
φ130*433 |
φ150*553 |
φ173*623 |
φ319*633 |
φ319*968 |
|
Trolley Frame Dimensions (Height*Width)mm |
/ |
/ |
/ |
/ |
900*300 |
1200*300 |
|
Filling Volume: ml(0-5%) |
2000 |
3000 |
6000 |
9000 |
25000 |
45000 |
|
Working Pressure(MPa) |
1.2 |
1.2 |
1.2 |
1.2 |
1.2 |
1.2 |
|
Minimum Effective Discharge Time (s) |
Class A:≥8 |
Class A:≥8 |
Class A:≥8 |
Class A:≥13 |
≥40
|
≥40 |
|
Time (S) |
Class B:≥9 |
Class B:≥9 |
Class B:≥9 |
Class B:≥9 |
||
|
Discharge Duration (M) |
≥3.0 |
≥3.0 |
≥3.0 |
≥3.0 |
≥6 |
≥6 |
|
Class A Fire Rating |
1A |
1A |
2A |
2A |
4A |
6A |
|
Class B Fire Rating |
55B |
55B |
70B |
89B |
183B |
233B |
|
Class E Fire Rating |
Conductivity meets standard requirements |
|||||
|
Class F Fire Rating |
5F |
5F |
25F |
40F |
/ |
/ |
|
Delay Time (s) |
≦5 |
≦5 |
≦5 |
≦5 |
≦5 |
≦5 |
|
Residue Rate (%) |
≦10 |
≦10 |
≦10 |
≦10 |
≦10 |
≦10 |
|
Hydraulic Test (MPa) |
2.1 |
2.1 |
2.1 |
2.1 |
2.1 |
2.1 |
|
Operating Temperature |
Normal Type: 0℃ ~ +60℃ ; Low Temp Type: -30℃ ~ +60℃ |
|||||
Related Products
Product Inquiry
We highly value your feedback and inquiries. If you have any questions about our products or services, please fill out the form below, and we’ll get in touch with you as soon as possible.